System Setup
4-19
Copyright
2001 Phone: (614) 771-2718 RE-4500
Vanner Inc. FAX: 614-771-4904 Owners Manual
4282 Reynolds Dr. www.vanner.com Rev 01e
Hilliard Ohio 43026 RE-Installation_Manual_Rev01e 910157-A
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
g.
And last, set "Charge Timeout" to "0.00 Hours." Press
the Top Right Key to take you back to “Charge Step
#”.
This charge step is a placeholder where nothing really
happens to the batteries until their voltage falls and they
truly do need a charge. At that point, the inverter charges
the batteries at 0 Adc until the battery voltage falls below
22.0 Vdc, and then goes on to the next charging step.
3.
Perform the second set of charging steps:
a.
Set "Charge Step #" to 2. (The second charging step)
Press the Top Right Key.
b.
Leave "Charge Stage " whatever it is, "BLKC?" Press
the Top Right Key.
c.
Choose the "Charge Type" to be "DC CURRENT."
Press the Top Right Key.
d.
Make the "Charge Setting" "100.0 Adc." (+100.0) (
50
A
DC
for the RE48-4500
) Press the Top Right Key.
e.
Choose the "End Chrg Type" to be ">=DC
VOLTAGE." Press the Top Right Key.
f.
Next make the "End Chrg Set'g" "27.20 Vdc" (
54.4
Vdc
for the RE48-4500) or whatever voltage is correct
for your battery bank. Press the Top Right Key
g.
And last, set "Charge Timeout" to "24.00 Hours".
Press the Top Right Key to take you back to “Charge
Step #”.
During this charging step the inverter will put 100 Adc (
50
A
DC
for the RE48-4500
) into the batteries until their
voltage has risen to 27.20 Vdc (
54.4 Vdc
for the RE48-
4500
) (or until 24 hours have gone by) and then the
inverter will go on to the next charging step.
4.
Perform the third set of charging steps:
a.
Set "Charge Step #" to 3. (The third and last charging
step) Press the Top Right Key.
b.
Leave "Charge Stage " whatever it is, "BLKV?" Press
the Top Right Key.
c.
Choose the "Charge Type" to be "DC VOLTAGE."
Press the Top Right Key.
d.
Make the "Charge Setting" "27.20 Vdc," (
54.4 Vdc
for
the RE48-4500
) the ending voltage of your last step.
Press the Top Right Key.
Vista de pagina 54