Vanner RE Series Manual de instalación Pagina 18

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 92
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 17
Installation And Start-Up
3-13
Copyright
2001 Phone: (614) 771-2718 RE-4500
Vanner Inc. FAX: 614-771-4904 Owners Manual
4282 Reynolds Dr. www.vanner.com Rev 01e
Hilliard Ohio 43026 RE-Installation_Manual_Rev01e 910157-A
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
been written for your protection and their requirements should
be followed.
(15) Battery Temperature Sensor Monitor Port
This RJ11 Port enables battery bank temperature monitoring
with the optional Vanner Battery Temperature Sensor (Vanner
Part Number RE-BTS1). This sensor is used for optimizing
battery charging efficiency, extending battery life, and battery
fault monitoring.
Warning
This connector is for the Battery Temperature Sensor only!
Attaching any other device to this connector can result in loss of
life, damage to the system, and voiding of your manufacturers
Warranty.
Check your terminations carefully!
(16) Relay A Contacts – Low Batt
These terminals are available to the user from the RE-4500 and
can be used for several programmable functions. These three
Terminals are designated as Normally Open, Common, and
Normally Closed.
This Relay’s factory default use is for
Low Battery Alert
.
(17) Relay B Contacts
These terminals are available to the user from the RE-4500 and
can be used for several programmable functions. These three
Terminals are designated as Normally Open, Common, and
Normally Closed.
This relay’s factory default use is undefined at this time.
(18) Relay C Contacts
These terminals are available to the user from the RE-4500 and
can be used for several programmable functions. These three
Terminals are designated as Normally Open, Common, and
Normally Closed.
This relay’s use is for the
Generator Start
Contacts.