(19) Relay D Contacts
These terminals are available to the user from the RE-4500 and
can be used for several programmable functions. These three
Terminals are designated as Normally Open, Common, and
Normally Closed.
This relay’s factory default use is undefined at this time.
(20) Control Relay Ground Terminal
This is a ground pin for the auxiliary output voltage from the
main DC bus. This terminal can be used for the creation of a
wetting voltage for the internal relay contacts
(21) Control Relay VDC
This is actually an unregulated auxiliary output voltage from
the main DC bus. In the case of the RE24-4500, this voltage
will be 24 V
DC
and can be used as a wetting voltage directly for
the internal relays. In the case of the RE48-4500 this voltage
will be 48 V
DC
and can be used to wet 48V
DC
contacts current
limited to 1 amp.
(22) Positive Termination From +VDC Power Source
Attach either +24 VDC or +48 VDC (depending on your
model) Positive feed to this terminal
Warning
Check Polarity Carefully! Attaching the Negative supply to this
terminal can result in loss of life, damage to the system, the
batteries, and voiding of Warranty.
Check your terminations carefully!
!!Make Certain that the proper voltage is connected to the unit –
24VDC for the RE24-4500, and 48VDC for the RE48-4500. Damage
will result if improper voltage is applied.
(23) Negative Termination From DC Power Source
Attach either +24 VDC or 48 VDC (depending on your model)
Negative (Ground) feed to this terminal.